PL12 |
NMT_Flow |
PL12 |
Command Group: MassFlow | Access: | Network interfaces: | ||
RW | CANopen | SDO2B00sub0C | ||
MODbus | 2516,2 | |||
PL12 - NMT_Flow | PROFIbus | read 42,12 write 42,140 |
|
|
PL12 No motion time - flow
The mass flow change detection provides a means for "freezing" the analog output whenever an instability condition or "change" is detected.
The condition "no change" or "stable state" is reached when the measurement signal for the time set in PL12 is stable and during this time does not fluctuate more than the "allowed" change range set in PL11.
The time set in PL12 is defined as PL12 x Δt where Δt is defined by PL3.
Setup range: 1 to 65535.