PL11

NMR_Flow

PL11


Command Group: MassFlow

Access:

Network interfaces:

RW

CANopen

SDO2B00sub0B

MODbus

2514,2

PL11 - NMR_Flow

PROFIbus

read 42,11 write 42,139


Synopsis:
CommandResponse
GetPL11P11:<Value>
SetPL11 <Value>OK (or ERR)
Valid forMin. valueMax. value
141.185 0 65535
142.185 0 65535
143.185 0 65535



PL11 No motion range - flow

The mass flow change detection provides a means for "freezing" the analog output whenever an instability condition or "change" is detected.
The condition "no change" or "stable state" is reached when the measurement signal for the time set in PL12 is stable and during this time does not fluctuate more than the "allowed" change range set in PL11.

Setup range: 1 to 65535.

See also  LS, LI, GF, GR, GM, PL1, PL2, PL3, PL4, PL5.
And for the DAD:  VF, GD, PL6, PL7, PL8, PL9, PL10, PL12, PL13, PL14, PL15, PL16, PL17, PL18, PL19, PL20, PL21, and AA