Command Group: Calibration | Access: | Network interfaces: | |
| TAC protected | RW | CANopen | |
| | MODbus | |
OF - Set Output Format | | PROFIbus | |
| Synopsis: |
| Command | Response |
| Get | OF | F<Value> |
| Set | OF <Value> | OK (or ERR) |
|
| Valid for | Min. value | Max. value |
| 141.181 |
0 |
3 |
| 141.184 |
0 |
3 |
| 141.185 |
0 |
3 |
| 141.186 |
0 |
3 |
| 142.181 |
0 |
3 |
| 142.184 |
0 |
3 |
| 142.185 |
0 |
3 |
| 142.186 |
0 |
3 |
| 143.181 |
0 |
3 |
| 143.184 |
0 |
3 |
| 143.185 |
0 |
3 |
| 151.181 |
0 |
3 |
| 151.184 |
0 |
3 |
| 151.186 |
0 |
3 |
| 152.181 |
0 |
3 |
| 152.184 |
0 |
3 |
| 162.181 |
0 |
3 |
| 179.181 |
0 |
3 |
| 181.181 |
0 |
3 |
| 64.181 |
0 |
3 |
| 64.184 |
0 |
3 |
| 69.181 |
0 |
3 |
| 78.183 |
0 |
3 |
|
OF Controls the Output format for
GG,
GN,
GL and
GW.
These formats supports multi range applications.
The values 0..3 selects a format to be used:
- 0 = No range indication and no decimal point in GL and GW answers.
- 1 = With range indication and no decimal point in GL and GW answers.
- 2 = No range indication and with decimal point in GL and GW answers.
- 3 = With range indication and with decimal point in GL and GW answers.
Overview of the formats:
| |
GG |
GN |
GL |
GW |
| 0 |
G+01.100 |
N+01.100 |
L+00100+01100010F |
W+00100+01100010F |
| 1 |
G1+01.100 |
N1+01.100 |
L1+00100+01100010F |
W1+00100+01100010F |
| 2 |
G+01.100 |
N+01.100 |
L+00.100+01.100010F |
W+00.100+01.100010F |
| 3 |
G1+01.100 |
N1+01.100 |
L1+00.100+01.100010F |
W1+00.100+01.100010F |
Note that indicated decimal points are shown as DP = 3.
See also
MR,
CM1,
CM2,
CM3,
DP,
GN,
GT.
GS,
GL,