FF |
Filter factor |
FF |
Command Group: Filter | Access: | Network interfaces: | ||
RW | CANopen | SDO2100sub05 | ||
MODbus | 2108,2 | |||
FF - Display filter factor | PROFIbus | read 18,5 write 31,5 |
|
|
FF Filter Factor (0-15) [DISPLAY MODE ONLY]. This command will define over how long time a rolling average will be calculated. A setting of 0 will result in an averaging over 200ms and a setting of 15 over 3.2 sec. Issuing the FF command without any parameters will return the current filter factor setting. Factory default setting: 0.
See also
FL,
FM,
UR.
General filter description.